不同运行工况下间接蒸发冷却器换热性能试验研究Experimental study on heat transfer performance of indirect evaporative cooler under various operating conditions
胡凯,郭春梅,李勇刚,由玉文,李美萱
HU Kai,GUO Chunmei,LI Yonggang,YOU Yuwen,LI Meixuan
摘要(Abstract):
为了研究间接蒸发冷却器作为组合式空调机组新风预冷装置在不同温湿度状况的换热效果,利用自主搭建的试验系统对8种不同运行模式下间接蒸发冷却器的换热过程进行了试验测试。结果显示:该装置较普通显热换热器换热效果更突出,干球效率能达到100%以上,湿球效率在60%~70%;通过将板式换热器从干工况运行模式切换到湿工况运行模式,可以显著降低一次空气出口温度;在干燥环境下,间接蒸发冷却技术具有良好的适用性,经过处理的室外新风能直接送入空调房间并能承担部分室内显热负荷;而在高温潮湿环境下,室外新风在换热过程中出现大量凝结,不仅减少了空调的显热负荷,而且减少了潜热负荷,且系统COP能够高达37.52。
In order to study the heat transfer effect of the indirect evaporative cooler as the fresh air precooling device of the combined air conditioning unit under different temperature and humidity conditions,the heat transfer process of the indirect evaporative cooler under eight different operation modes was tested using the self built experimental system.The results show that:compared with ordinary sensible heat exchanger,the device has more outstanding heat transfer effect,its dry bulb efficiency can reach more than 100%,and the wet bulb efficiency can reach 60%~70%;by switching the plate heat exchanger from dry operation mode to wet operation mode,the primary air outlet temperature can be significantly reduced;in dry environment,the indirect evaporative cooling technology has good applicability,the treated outdoor fresh air can be directly sent to the air-conditioned room and bear part of the indoor sensible heat load;whereas in the high temperature and humid environment,a lot of condensation appears in the heat exchange process of outdoor fresh air,which not only reduces the sensible heat load of the air conditioning,but also reduces the latent heat load,and the COP of the system can reach as high as 37.52.
关键词(KeyWords):
间接蒸发冷却;新风预冷;干工况;湿工况;COP
indirect evaporative cooler;fresh air pre-cooling;dry cooling condition;wet cooling condition;COP
基金项目(Foundation): 国家自然科学基金项目(51678385)
作者(Author):
胡凯,郭春梅,李勇刚,由玉文,李美萱
HU Kai,GUO Chunmei,LI Yonggang,YOU Yuwen,LI Meixuan
参考文献(References):
- [1]LUIS P L,JOSE O,CHRISTINE P.A review on buildings energy consumption information[J].Energy and Buildings,2008,40(3):394-398.
- [2]DUAN Z Y,ZHAN C H,ZHANG X X,et al.Indirect evaporative cooling:Past,present and future potentials[J].Renewable and Sustainable Energy Reviews,2012,16:6823-6850.
- [3]黄翔.面向环保、节能、经济及室内空气品质联合挑战的蒸发冷却技术[J].建筑热能通风空调,2003,22(4):1-4.HUANG X.Evaporative cooling technology facing the joint challenge of environmental protection,energy conservation,economy and indoor air quality[J].Building Thermal Ventilation and Air Conditioning,2003,22(4):1-4.
- [4]TULSIDASANI T R,SAWHNEY R L,SINGH S P,et al.Recent research on an indirect evaporative cooler(IEC)part 1:Optimization of the COP[J].Int.J.Energy Res.,1997,21(12):1099-1108.
- [5]樊丽娟,黄翔,吴志湘.管式间接蒸发冷却系统中强化管外传热传质方法的对比分析[J].流体机械,2008,36(11):47-51.FAN L J,HUANG X,WU Z X.Comparative analysis of heat and mass transfer enhancement methods outside tube in tubular indirect evaporative cooling system[J].Fluid Machinery,2008,36(11):47-51.
- [6]DUAN Z,ZHAN C,ZHAO X,et al,Experimental study of a counter-flow regenerative evaporative cooler[J].Building and Environment,2016,104:47-58.
- [7]刘佳莉,黄翔,韩正林,等.干燥工况下新型复合式露点间接蒸发冷却空调机组的试验研究[J].流体机械,2015,43(3):52-57.LIU J L,HUANG X,HAN Z L,et al.Experimental study on a new compound dew point indirect evaporative cooling air conditioning unit under dry condition[J].Fluid Machinery,2015,43(3):52-57.
- [8]孙铁柱,黄翔,罗绒.采用不同二次空气时转轮式间接蒸发冷却器的性能试验研究[J].流体机械,2015,43(5):65-69.SUN T Z,HUANG X,LUO R.Experimental study on performance of rotary indirect evaporative cooler with different secondary air[J].Fluid Machinery,2015,43(5):65-69.
- [9]赵振生,任承钦,曾阳,等.加导流条的间接蒸发冷却器性能实验研究[J].化学工程,2010,38(6):31-34.ZHAO Z S,REN C Q,ZENG Y,et al.Experimental study on performance of indirect evaporative cooler with guide strip[J].Chemical Engineering,2010,38(6):31-34.
- [10]WANG F H,SUN T Z,HUANG XIANG,et al.Experimental research on a novel porous ceramic tube type indirect evaporative cooler[J].Applied Thermal Engineering,2017,125:1191-1199.
- [11]LEE J,LEE D Y.Experimental study of a counter flow regenerative evaporative cooler with finned channels[J].Int.J.Heat Mass Transf,2013,65(5):173-179.
- [12]李晗,吕建,孟丹东,等.间接蒸发冷却器二次空气的试验研究[J].流体机械,2019,47(3):75-78.LI H,LYU J,MENG D D,et al.Experimental study on secondary air in indirect evaporative cooler[J].Fluid Machinery,2019,47(3):75-78.
- [13]李晗,吕建,李勇刚,等.新风风量对间接蒸发冷却器冷凝区域和性能的影响[J].流体机械,2019,47(10):75-81.LI H,LYU J,LI Y G,et al.Influence of fresh air flow rate on condensation area and performance of indirect evaporative cooler[J].Fluid Machinery,2019,47(10):75-81.
- [14]李晗,吕建,李勇刚,等.风量比对间接蒸发冷却器性能影响的试验研究[J].流体机械,2019,47(7):56-60.LI H,LYU J,LI Y G,et al.Experimental study on the effect of air volume ratio on the performance of indirect evaporative cooler[J].Fluid Machinery,2019,47(7):56-60.
- [15]许晶晶,黄翔,张鸿,等.公共场所用单元式蒸发冷却空调的设计与测试分析[J].流体机械,2019,47(9):84-88.XU J J,HUANG X,ZHANG H,et al.Design and test analysis of unitary evaporative air cooling for public place[J].Fluid Machinery,2019,47(9):84-88.
- [16]王玉刚,黄翔.叉流式露点蒸发冷却器冷却性能的数值模拟[J].流体机械,2019,47(4):69-75.WANG Y G,HUANG X.Numerical simulation of the cooling performance of a cross-flow dew point evaporative cooler[J].Fluid Machinery,2019,47(4):69-75.
- [17]CHEN Y,YANG H X,LUO Y M.Indirect evaporative cooler considering condensation from primary air:Model development and parameter analysis[J].Building and Environment,2016,95:330-345.