基于最优COP的楼宇空调冷水机组间的负荷优化分配Optimal Loading Strategy of Multiple Chillers in HVAC Based on COP Optimization
陈丹丹,晋欣桥,杜志敏,肖晓坤
CHEN Dan-dan,JIN Xin-qiao,DU Zhi-min,XIAO Xiao-kun(Shanghai Jiaotong University
摘要(Abstract):
多台冷水机组联合运行系统中,各冷水机组系统大部分时间处于部分负荷运行状态。根据冷水机组COP与其负荷率(PLR)之间关系特性,提出一种自适应的负荷优化分配方法,分别根据具有相同和不同额定制冷量冷水机组的系统,对此方法进行了介绍,并与使用回归方法获取PLR与COP关系的策略进行了比较,发现节能效果更明显。
In the multiple chillers system,the chillers are usually loaded partly in the most of running times.According to the relationship between COP and PLR of the system,an optimal loading strategy is presented.Adaptive method is employed to obtain the relation between PLR and COP,and the objective function of chillers system energy consumption is set up to obtain the optimal PLR through optimizing.The simulation results show that the strategy of using adaptive method to obtain the relationship between PLR and COP and incorporating it into online control in the multiple chillers system is better than regression method for saving energy.
关键词(KeyWords):
冷水机组;负荷分配;自适应;优化控制;负荷率
chiller;optimal loading;adaptive method;optimal control;part load ratio(PLR)
基金项目(Foundation):
作者(Author):
陈丹丹,晋欣桥,杜志敏,肖晓坤
CHEN Dan-dan,JIN Xin-qiao,DU Zhi-min,XIAO Xiao-kun(Shanghai Jiaotong University
参考文献(References):
- [1]晋欣桥,李晓锋,任海刚.楼宇空调变水量冷媒水系统实时优化控制[J].上海交通大学学报,2003,37(7):1128-1132.
- [2]Braun J E.Applications of Optimal Control to ChilledWater Systems without Storage[J].ASHRAE Transac-tions,1989,95(PartⅠ):663-675.
- [3]蔡宣三.最优化与最优控制[M].北京:清华大学出版社,1982.
- [4]Klein S A.TRNSYS:A Transient system simulationprogram--Version 13.1[M].USA:University of Wis-consin-Madison,1990.
- [4]Yang Chungchang.A novel energy conservation meth-od-optimal chiller loading[J].Electric Power SystemsResearch,2004,69(2-3):221-226.