溶液调湿空调系统浓度差的变化规律研究Research on Solution Concentration Difference of Liquid Desiccant Systems
夏燚,张烨,汪峰
XIA Yi,ZHANG Ye,WANG Feng
摘要(Abstract):
从理论上分析了溶液分支流量对溶液平衡浓度差的影响,给出了溶液平衡浓度差的理论计算模型。模拟计算结果表明:随着溶液分支流量的增大,浓溶液和稀溶液之间的平衡浓度差减小;在相同的溶液分支流量下,Li Cl溶液的平衡浓度差比Li Br溶液略大;系统冷负荷和热负荷增加量均随溶液分支流量的增大而增大,但随板式换热器进出口溶液温差的增大而减小;与Li Br溶液相比,Li Cl溶液循环过程受溶液分支流量的影响相对较大。
The effect of the solution branch flow on solution equilibrium concentration difference based on the theoretical analysis was proposed,and the calculation model of solution equilibrium concentration difference was presented. The simulation results illustrated that with the increasing of the equilibrium concentration of solution branch flow,solution concentration difference between strong solution and weak solution decreases; and that in the same solution branch flow rate,the equilibrium concentration of Li Cl solution was slightly larger than Li Br solution; and the cooling capacity and heating capacity of the heat pump system increased while the solution branch flow rate increased,and decreased with the decrease of inlet-and-outlet solution temperature of the plate heat exchanger; and that compared with Li Br solution,Li Cl solution circulation was more likely affected by solution branch flow rate.
关键词(KeyWords):
溶液调湿;分支流量;平衡浓度差
liquid-desiccant;branch flow rate;balance concentration difference
基金项目(Foundation): “十二五”国家科技支撑计划资助项目(2011BAJ03B10);; 江苏省高校自然科学研究项目(14KJB470007)
作者(Author):
夏燚,张烨,汪峰
XIA Yi,ZHANG Ye,WANG Feng
参考文献(References):
- [1]陈晓阳,丛琳,张婷,等.溶液调湿空气处理技术的研究进展[J].暖通空调,2011,41(1):21-27.
- [2]张伟程,滕汜颖.溶液调湿新风机组与地源热泵相结合的空调设计[J].暖通空调,2013,42(2):21-27.
- [3]Liu X H,Qu K Y,Jiang Y.Empirical correlations to predict performance of the dehumidifier using liquid desiccant in heat and mass transfer[J].Renewable Energy,2006,31(10):1267-1639.
- [4]宣永梅,肖赋.香港地区溶液除湿与蒸发冷却复合系统的节能分析[J].建筑科学,2009(2):84-87.
- [5]黄志甲,鲁月红,雷博,等.溴化锂溶液除湿器性能的实验研究[J].化工学报,2012,61(S2):81-85.
- [6]Yin Y G,Zhang X S,Chen Z Q.Experimental study on dehumidifier and regenerator of liquid desiccant cooling air conditioning system[J].Building and Environment,2007,42(7):2505-2511.
- [7]杨金伟,裴刚,林媛,等.溴化锂溶液除湿系统再生过程实验研究[J].热科学与技术,2011,10(4):345-350.
- [8]陈洋,周大庆,李玲玉,等.水动冷却塔直驱混流式水轮机转轮数值模拟优化[J].排灌机械工程学报,2014,32(7):600-605.
- [9]黄志甲,姜萍,周立宁.溶液除湿过程热质耦合的理论分析与数值模拟[J].流体机械,2014,42(2):67-71,82.
- [10]魏小兵,江楠,曾纪成.长径比对油冷却器传热及综合性能的影响[J].化工设备与管道,2013,50(1):29-32.
- [11]Tu M,Ren C Q,Zhang LAi,et al.Simulation and analysis of a novel liquid desiccant air-conditioning system[J].Applied Thermal Engineering,2009,29(11/12):2417-2425.
- [12]黄志甲,王玉忠,周立宁.Li Br溶液除湿系统再生器性能正交试验研究[J].流体机械,2014,42(8):69-72,6.
- [13]左学兵,陈晶晶,张金东,等.AP1000反应堆冷却剂系统主要设备安装技术[J].压力容器,2013,30(11):62-69,75.
- [14]高文忠,柳建华,章学来.太阳能叉流溶液除湿空调除湿性能试验分析[J].太阳能学报,2012,33(9):1547-1552.
- [15]熊珍琴,代彦军,王如竹.热致浓度差溶液除湿系统性能优化与分析[J].暖通空调,2008,38(11):89-93.