间接蒸发冷却器二次空气的试验研究Experimental Study on Secondary Air of Indirect Evaporative Cooler
李晗,吕建,孟丹东,郭春梅,马雪健,许继祥
Li Han,Lv Jian,Meng Dandong,Guo chunmei,Ma Xuejian,Xu Jixiang
摘要(Abstract):
通过搭建可视化的间接蒸发冷却试验系统,研究了无冷凝、部分冷凝、全冷凝条件下新风温湿度和风量对间接蒸发冷却器二次空气的影响。试验结果显示,冷凝可以有效地抑制二次空气的温降,增加二次空气的含湿量;在全冷凝条件下新风温湿度过高则会出现二次空气温升。另外,冷凝条件下新风风量对二次空气温湿度影响较小。
In this paper,the effect of fresh air temperature,relative humidity and volume flow on secondary air of indirect evaporative cooler under non-condensation,partial condensation and total condensation conditions was investigated by building a visualized test system of the indirect evaporative cooler. The test results show that condensation can significantly suppress temperature drop of secondary air,and increase its moisture content. When the temperature and relative humidity of fresh air are too high under total condensation condition,temperature rise of secondary air will occur. Furthermore,the effect of fresh air volume flow under condensation condition on secondary air is relatively small.
关键词(KeyWords):
新风;二次空气;冷凝;温差;含湿量差
fresh air;secondary air;condensation;temperature difference;difference of moisture content
基金项目(Foundation): 国家自然科学基金资助项目(51678385)
作者(Author):
李晗,吕建,孟丹东,郭春梅,马雪健,许继祥
Li Han,Lv Jian,Meng Dandong,Guo chunmei,Ma Xuejian,Xu Jixiang
参考文献(References):
- [1]Pandelidis D,Anisimov S,Worek W.M.Comparison study of the counter-flow regenerative evaporative heat exchangers with numerical methods[J].Applied Thermal Engineering,2015,84:211-224.
- [2]Yi C,Luo Y,Yang H.A simplified analytical model for indirect evaporative cooling considering condensation from fresh air:Development and application[J].Energy&Buildings,2015,108(3):387-400.
- [3]Antonellis S D,Joppolo C M,Liberati P,et al.Experimental analysis of a cross flow indirect evaporative cooling system[J].Energy&Buildings,2016,121:130-138.
- [4]Riangvilaikul B,Kumar S.An experimental study of a novel dew point evaporative cooling system[J].Energy&Buildings,2010,42(11):2241-2250.
- [5]Riangvilaikul B,Kumar S.An experimental study of a novel dew point evaporative cooling system[J].Energy&Buildings,2010,42(11):2241-2250.
- [6]Lee J,Choi B.S,Lee D.Y.Comparison of configurations for a compact regenerative evaporative cooler[J].International Journal of Heat&Mass Transfer,2013,65(5):192-198.
- [7]Song C H,Lee D Y,Ro S T.Cooling enhancement in an air-cooled finned heat exchanger by thin water film evaporation[J].International Journal of Heat&Mass Transfer,2003,46(7):1241-1249.
- [8]Bruno F.On-site experimental testing of a novel dew point evaporative cooler[J].Energy&Buildings,2011,43(12):3475-3483.
- [9]Ahmad A,Rehman S,Al-Hadhrami L M.Performance evaluation of an indirect evaporative cooler under controlled environmental conditions[J].Energy&Buildings,2013,62(7):278-285.
- [10]Bolotin S,Vager B,Vasilijev V.Comparative analysis of the cross-flow indirect evaporative air coolers[J].International Journal of Heat&Mass Transfer,2015,88:224-235.
- [11]薛运,黄翔,申长军,等.空气侧间接蒸发冷却二次排风的再利用[J].制冷与空调(四川),2016,30(2):132-135.
- [12]Chen Yi,Yang Hongxing,Luo Yimo.Indirect evaporative cooler considering condensation from primary air:Model development and parameter analysis[J].Building&Environment,2016,95:330-345.
- [13]Chen Yi,Yang Hongxing,Luo Yimo.Experimental study of plate type air cooler performances under four operating modes[J].Building&Environment,2016,104:296-310.
- [14]Chen Yi,Yang Hongxing.A simplified analytical model for indirect evaporative cooling considering condensation from fresh air:Development and application[J].Energy&Buildings,2015,108(3):387-400.
- 新风
- 二次空气
- 冷凝
- 温差
- 含湿量差
fresh air - secondary air
- condensation
- temperature difference
- difference of moisture content