流体机械

2015, v.43;No.519(09) 63-66+82

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

毛细管空调与传统空调的空气调节性能的对比试验
Experiment of Performance Comparison between Capillary Radiation Air Conditioning and Traditional Air Conditioning

陈慧,韩东太,刘磊
CHEN Hui,HAN Dong-tai,LIU Lei

摘要(Abstract):

以能源与动力工程实验中心节能减排实验室为背景,对毛细管空调系统与传统空调进行制冷及除湿性能对比实验。监测室内温湿度分布情况;结果显示:毛细管辐射空调运行时,在人体主要活动范围内温度平均在25.5~27.3℃,相对湿度在56.8%~65.0%;对比毛细管辐射空调运行时,传统空调温度分布均匀性较差,温度在25.0~26.3℃之间,垂直方向上随着高度升高逐渐降低,水平方向上各测点的温度分布不均。这种温度分布使得人体有忽冷忽热的感觉,各测点相对湿度波动较明显,但是垂直和水平方向的相对湿度值相差在5%以内,较毛细管辐射空调供冷相对湿度区间较小。
The background is energy conservation laboratory of Energy and Power Engineering Experimental Center in the University of Mining and Technology. Conduct cooling and dehumidification experiments for capillary air conditioning and the traditional air conditioning. The experimental results show that average temperature range in main area is between 25. 5℃ and 27. 3℃when capillary air conditioning works,and the relative humidity range is between 56. 8% and 65. 0%. Compared with capillary air conditioning,Traditional air conditioning has a worse temperature distribution. The temperature is between 25. 0 ℃ and 26. 3℃,it gradually reduces with height increases in the vertical direction and unevenly distributes in horizontal direction. This distribution has the feeling of hot and cold and the relative humidity fluctuates obviously. But relative humidity difference in 5% of vertical and horizontal direction,relative humidity section is smaller compared with the capillary air conditioning.

关键词(KeyWords): 毛细管;辐射;传统空调;温度;相对湿度
capillary;radiation;traditional air conditioning;temperature;relative humidity

Abstract:

Keywords:

基金项目(Foundation): 江苏省研究生教育教学改革研究与实践课题5-能源动力类研究生自主创新实验平台建设(JGLX13_10);; 中国矿业大学2011年课程建设与教学改革项目(201160);; 校级大学生新能源与节能减排实践基地建设资助项目

作者(Author): 陈慧,韩东太,刘磊
CHEN Hui,HAN Dong-tai,LIU Lei

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享