R152a在无油直线压缩机中应用的试验研究Experimental research on the application of R152a in oil-free linear compressor
鲍鑫,沈浩,陈新文,王翔,骆桢弘,李兆华
BAO Xin,SHEN Hao,CHEN Xinwen,WANG Xiang,LUO Zhenhong,LI Zhaohua
摘要(Abstract):
为进一步降低制冷剂R134a对全球变暖的影响并提高蒸气压缩制冷(VCR)系统的性能,使用R152a作为替代制冷剂,同时为避免润滑油对制冷剂性能评估的影响,采用由无油直线压缩机组成的VCR系统,在不同压缩机行程与压力比的工况下,对制冷剂R152a和R134a的性能进行了对比试验研究。研究结果表明,在压力比为2.5,压缩机行程为11 mm时,R152a的功率输入比R134a低17%,平均相差10 W;在压缩机行程为12 mm,压力比为2.0时,R152a与R134a均获得最大质量流量,分别为2.2 g/s和2.8 g/s;在固定压力比下,R152a的容积效率高于R134a,平均容积效率高约16%;在压力比为2.0和压缩机行程为12 mm时,R152a和R134a的制冷量分别为464 W和414 W。R152a的平均制冷量比R134a高13%左右;R152a和R134a的COP(性能系数)分别为6.5和5.3,R152a的平均COP比R134a高14%左右。
To further reduce the global warming impact of refrigerant R134a and to improve the performance of VCR(vapor compression refrigeration) systems,R152a was used as an alternative refrigerant and to avoid the influence of lubricating oil on the evaluation of refrigerant performance,a comparative experimental study of the performance of refrigerants R152a and R134a was conducted using a VCR system consisting of an oil-free linear compressor under the operating conditions of different compressor stroke and pressure ratio.The results indicate that at a pressure ratio of 2.5 and a compressor stroke of 11 mm,the power input of R152a is 17% lower than that of R134a,with an average difference of 10 W. At a compressor stroke of 12 mm and a pressure ratio of 2.0,both R152a and R134a achieve maximum mass flow rates of 2.2 g/s and 2.8 g/s,respectively.At a fixed pressure ratio,R152a has a higher volumetric efficiency than R134a,with an average volumetric efficiency of approximately 16%. At a pressure ratio of 2.0 and a compressor stroke of 12 mm,the cooling capacities of R152a and R134a are 464W and 414W respectively.The average cooling capacity of R152a is about 13% higher than that of R134a. The COP(coefficient of performance) of R152a and R134a are 6.5 and 5.3,respectively.The average COP of R152a is about 14% higher than that of R134a.
关键词(KeyWords):
R152a;无油;直线压缩机;压缩机行程;压力比
R152a;oil-free;linear compressor;compressor stroke;pressure ratio
基金项目(Foundation): 江苏省青年基金项目(BK20210820);; 江苏省研究生科研与实践创新计划项目(XSJCX20_019)
作者(Author):
鲍鑫,沈浩,陈新文,王翔,骆桢弘,李兆华
BAO Xin,SHEN Hao,CHEN Xinwen,WANG Xiang,LUO Zhenhong,LI Zhaohua
参考文献(References):
- [1]王乐乐,戴源德,姜毅,等.低GWP混合工质RE170/R134a用于汽车空调的性能分析[J].流体机械,2020,48(10):76-82.WANG L L,DAI Y D,JIANG Y,et al.Performance study of low GWP mixed refrigerant RE170/R134a used in automobile air conditioner[J].Fluid Machinery,2020,48(10):76-82.
- [2]孙维栋,张鹏,张昌.R1234yf/R134a二元混合工质的热物理性质[J].流体机械,2017,45(8):78-83.SUN W D,ZHANG P,ZHANG C.The thermophysical properties of binary mixed refrigerant R1234yf/R134a[J].Fluid Machinery,2017,45(8):78-83.
- [3]谢锦涛,吕奕明,王定标,等.新型混合制冷剂R744/R152a的热力学性能评价[J].低温与超导,2021,49(6):93-98.XIE J T,LU Y M,WANG D B,et al.Thermodynamic performance evaluation of a new mixed refrigerant R744/R152a[J].Cryogenics&Superconductivity,2021,49(6):93-98.
- [4]刘馨,张卫军,曹琬,等.R1234yf套管式蒸发器模拟研究[J].流体机械,2019,47(9):67-71.LIU X,ZHANG W J,CAO W,et al.Simulation of double-tube evaporator with R1234yf[J].Fluid Machinery,2019,47(9):67-71.
- [5]钟晓晖,曹春蕾,李晓娟,等.风能直接驱动R134a/R123复叠式热泵系统运行特性研究[J].流体机械,2018,46(4):84-88.ZHONG X H,CAO C L,LI X J,et al.Research on operation characteristics of R134a/R123 cascade heat pump system driven by wind power[J].Fluid Machinery,2018,46(4):84-88.
- [6]吴龙兵,苏林,方奕栋,等.R1234yf汽车空调性能KULI仿真分析[J].流体机械,2017,45(8):68-72.WU L B,SU L,FANG Y D,et al.R1234yf mobile air conditioning performance simulation analysis using KULI[J].Fluid Machinery,2017,45(8):68-72.
- [7]郭志旺,王彬,祁影霞.制冷剂R1234yf水合物的试验研究[J].流体机械,2017,45(4):58-62.GUO Z W,WANG B,QI Y X.Experimental study of R1234yf refrigerant hydrate[J].Fluid Machinery,2017,45(4):58-62.
- [8]胡文举,王梦圆,江辉民,等.闪发蒸汽冷却技术及R134a用于高温空调器的研究[J].流体机械,2015,43(10):73-78.HU W J,WANG M Y,JIANG H M,et al.Study on the high temperature air-conditioner based on flash evaporative cooling technology and using R134a as refrigerant[J].Fluid Machinery,2015,43(10):73-78.
- [9]GANG LI,MAGNUS EISELE,HOSEONG LEE,et al.Experimental investigation of energy and exergy performance of secondary loop automotive airconditioning systems using low-GWP(global warming potential)refrigerants[J].Energy,2014,68:819-831.
- [10]VERMA,JITENDRA KUMAR,ANKIT SATSANGI,et al.A review of alternative to R134a(CH3CH2F)refrigerant[J].International Journal of Emerging Technology and Advanced Engineering,2013,3(1):300-304.
- [11]CABELLO R,SáNCHEZ D,LLOPIS R,et al.Energy evaluation of R152a as drop in replacement for R134a in cascade refrigeration plants[J].Applied Thermal Engineering,2017,110:972-984.
- [12]冯永斌,晏刚,钱文波.新型混合制冷剂R1270/R152a/R13I1的理论研究[J].制冷学报,2010,31(1):27-30.FENG Y B,YAN G QIAN W B.Theoretical study on a new mixed refrigerant R1270/R152a/R13I1[J].Journal of Refrigeration,2010,31(1):27-30.
- [13]孙维栋,孔祥敏,张娅玲,等.R1234yf/R152a用作汽车空调制冷剂的配比范围研究[J].节能,2020,39(1):90-96.SUN W D,KONG X M,ZHANG Y L,et al.Study on mole fraction range of R1234yf/R152a used as refrigerant for vehicle air-conditioning[J].Energy Conservation,2020,39(1):90-96.
- [14]CABELLO R,SáNCHEZ D,LLOPIS R,et al.Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor[J].International Journal of Refrigeration-revue Internationale Du Froid,2015,3(5):92-105.
- [15]MOHANRAJ M,JAYARAJ S,MURALEEDHARAN C.Comparative assessment of environment-friendly alternatives to R134a in domestic refrigerators[J].Energy Efficiency,2008,1(3):189-198.
- [16]陈江艳,杨诚.汽车空调润滑油最佳加注量试验方法研究[J].流体机械,2020,48(1):66-70.CHEN J Y,YANG C.Experimental study on the optimum filling amount of lubricating oil in automobile air conditioning system[J].Fluid Machinery,2020,48(1):66-70.