为研究双冷源新风机组在夏季供冷时的实际除湿效果,对双冷源新风机组在其名义工况下的除湿效果进行了试验测试,同时还研究了双冷源新风机组在不同主机供水温度、不同再热前温度、不同送风量等工况下的除湿效果。通过对双冷源新风机组在夏季实际运行时的除湿性能进行测试可以发现:双冷源新风机组在其名义工况下运行时单位质量新风的除湿量在18~25 g/kg之间,出风含湿量为8 g/kg,除湿效果良好;提高主机供水温度、提高再热前温度、增大送风量都会降低双冷源新风机组的除湿能力,使送风含湿量升高。研究结果对制定双冷源新风机组在实际应用时的运行策略都具有一定的参考价值。
In order to study the actual dehumidification effect of the double-cold source fresh air handling unit in summer,the dehumidification effect of the double-cold source fresh air handling unit under its nominal operating conditions was studied through experimental testing.At the same time,the dehumidification effect of the fresh air handling unit with double cold sources was also studied under different supply water temperature of the main unit,different temperature before reheating and different air volume.It can be found that the dehumidification capacity of fresh air per unit mass of double-cold source fresh air handling unit under its nominal operating conditions is between 18 g/kg and 25 g/kg,the outlet air humidity of the double-cold source fresh air handling unit is 8 g/kg under its nominal operating conditions,and the dehumidification effect is good.Moreover,the dehumidification capacity of the double-cold source fresh air handling unit will be reduced by increasing supply water temperature of the main unit,the temperature before reheating,and the supply air volume and the humidity of supply air be increased.The research results provide a certain reference value for developing the operation strategy of double-cold source fresh air handling units in practical application.
关键词(KeyWords):
双冷源新风机组;供水温度;再热前温度;除湿能力
double-cold source fresh air handling unit;supply water temperature;temperature before reheating;dehumidification capacity
基金项目(Foundation): 国家自然科学基金项目(11902188)
作者(Author):
宗天晴,王永彬,曹振,傅允准
ZONG Tianqing,WANG Yongbin,CAO Zhen,FU Yunzhun
参考文献(References):
- [1]殷平.磁悬浮离心式冷水机组和独立新风系统(1):现状[J].暖通空调,2013,43(12):91-100.YIN P.Magnetic levitation centrifugal chiller and independent fresh air system(1):present situation[J].HV&AC,2013,43(12):91-100.
- [2]陈剑波,李美玲,韩星.辐射空调用节能新风控温除湿机除湿性能实验研究[J].制冷学报,2015,36(3):79-86.CHEN J B,LI M L,HAN X.Experimental study on dehumidification performance of energy-saving fresh air temperature-controlled dehumidifier for radiation air conditioning[J].Journal of Refrigeration,2015,36(3):79-86
- [3]李鹏魁,傅允准.两级新风除湿机与毛细管辐射供热联合运行特性实验研究[J].轻工机械,2019,37(2):75-79.LI P K,FU Y Z.Experimental study on combined operation characteristics of two-stage fresh air dehumidifier and capillary radiation heating[J].Light Industrial Machinery,2019,37(2):75-79.
- [4]KANG Z,LI J,LI Z.Energy-saving analysis of cold and heat recovery of the full fresh air dehumidifier[J].Procedia Engineering,2017,205:4117-4121.
- [5]GALVIN R.Solving mould and condensation problems:A dehumidifier trial in a suburban house in Britain[J].Energy &Buildings,2010,42(11):2118-2123.
- [6]陈旭,孙金栋,李培方.板翅式新风机组实际运行性能影响因素[J].建筑科学,2020,36(10):92-100.CHEN X,SUN J D,LI P F.Factors affecting the actual operation performance of plate-fin fresh air unit[J].Architectural Science,2020,36(10):92-100.
- [7]翁文兵,刁海健,范志伟.串列式双蒸发温度新风机组的性能研究[J].流体机械,2020,48(6):84-88.WENG W B,DIAO H J,FAN Z W.Study on the performance of tandem double evaporation temperature fresh air unit[J].Fluid Machinery,2020,48(6):84-88.
- [8]吉煜.热湿地区温湿度独立控制空调系统的双冷源新风机组运行性能及适用性分析[D].广州:广州大学,2020.JI Y.Operation performance and applicability analysis of double cold source fresh air unit of temperature and humidity independent control air conditioning system in hot and humid area[D].Guangzhou:Guangzhou University,2020.