基于MATLAB的全封闭涡旋压缩机性能的仿真Performance Simulation of Hermetic Scroll Compressor Based on MATLAB Platform
郎铁军,马国远,马立章
LANG Tie-jun1,2,MA Guo-yuan1
摘要(Abstract):
从空调企业对压缩机仿真性能需求的实际出发,采用美国空调与制冷协会标准ANSI/ARI 540提供的"三次方十系数"方法对某品牌的定转速涡旋压缩机进行了性能参数的仿真模型建立,同时对压缩机质量流量和输入功率进行了吸气过热度的修正。在制冷剂物性计算方面本文采用了NIST Refprop7.0物性计算软件,通过Refprop在Matlab仿真程序中的调用顺利实现热物性与传输特性计算。该压缩机仿真模型精度较高且调用方便,为制冷系统仿真奠定了基础。
Taking into account the air-conditioning manufacturers' actual demands,according to the ANSI/ARI Standard 540's the standard 3rd order polynomial with ten coefficients,a fixed rotate speed scroll compressor's performance parameter simulation model is built about some brand,and some approach is used to correct the refrigerant mass and power input on account of the variations of superheat.NIST Refprop7.0 is used to calculate the refrigerant properties,and the calculation of refrigerant's thermodynamic and transfer properties is achieved by calling back the Refprop on Matlab Platform.The compressor simulation model has higher accuracy and is easy to callback and to lay the foundation for refrigeration system simulation.
关键词(KeyWords):
涡旋压缩机;仿真模型;系数法;吸气过热度;Matlab编程
scroll compressor;simulation model;coefficient method;suction superheat,Matlab program
基金项目(Foundation): 国家自然科学基金项目(50776001)
作者(Author):
郎铁军,马国远,马立章
LANG Tie-jun1,2,MA Guo-yuan1
参考文献(References):
- [1]Chen Y,Halm N P,Groll E A,et al.Mathematicalmodeling of scroll compressor-Part I:Compressionprocess modeling[J].International Journal of Refrig-eration,2002,25:731-750.
- [2]王宝龙,石文星.制冷空调用涡旋压缩机数学模型[J].清华大学学报(自然科学版),2005,45(6):
- [3]季杰,裴刚,何伟.空调-热水器一体机制冷兼制热水模式的性能模拟和实验分析[J].2003,33(2):19-23.
- [4]Marie-Eve Duprez E D M F.Modelling Of Reciproca-ting And Scroll Compressors[J].International Journalof Refrigeration,2007,30:873-886.
- [5]Performanc ration of positive displacement refrigerantcompressors and compressor units.ANSI/ARI Standard540[S].
- [6]苏顺玉,秦妍,赵之海,刘伟.涡旋压缩机的实验研究及其工作性能分析[J].流体机械,2006,34(10):1-4.
- [7]Stefan S Bertsch E A G.Two-Stage Air-SourceHeat Pump For Residential Heating And Cooling Ap-plications In Northern U.S.Climates[J].InternationalJournal of Refrigeration,2008,31:1282-1292.
- [8]Dabiri A E,Rice C K A compressor simulation modelwith corretions for the level of suction gas superheat[J].ASHRAE Transactions,1981,87(2):771-780.
- [9]REFPROP.NIST Standard Reference Database 23.Version 7.0[S].