新风送风方式对辐射吊顶制冷量影响研究Study on the Influence of Air Supply Modes on Cooling Capacity of Radiant Ceiling
金梧凤,王成,崔奉洙,王志强,于志浩
Jin Wufeng,Wang Cheng,Choi Bongsoo,Wang Zhiqiang,Yu Zhihao
摘要(Abstract):
为解决辐射吊顶在制冷量和消除湿负荷方面的不足,辐射吊顶加独立新风系统成为了国内外学者们的重点研究对象。通过对贴附射流、置换通风加辐射吊顶系统的比较试验,研究新风的不同送风方式对辐射空调系统制冷能力的影响。结果表明:贴附射流送风方式主要通过增大对流换热量提升辐射空调制冷量,相较于置换通风,其总制冷量有所提高,其中对流换热量提高34.29%,但辐射换热量却有所降低。
In order to solve the problem of cooling capacity and eliminating wet load,the radiant ceiling plus independent fresh air system has become the focus of scholars at home and abroad.The effect of different air supply modes on the cooling capacity of radiant air conditioning system was studied by comparing the attached jet,displacement ventilation and radiant ceiling systems.The results show that the results show that:the attached jet air supply mode mainly increases the cooling capacity of radiant air conditioning by increasing the convection heat transfer.Compared with the displacement ventilation,the total cooling capacity is improved,in which the convection heat transfer is increased by 34.29%,but the radiation heat transfer is reduced.
关键词(KeyWords):
辐射吊顶;贴附射流;置换通风;制冷能力
radiant ceiling;attached jet;displacement ventilation;cooling capacity
基金项目(Foundation):
作者(Author):
金梧凤,王成,崔奉洙,王志强,于志浩
Jin Wufeng,Wang Cheng,Choi Bongsoo,Wang Zhiqiang,Yu Zhihao
参考文献(References):
- [1] Koo S Y,Kim Y Y,Seok H T,et al.A study on the applicability of radiant cooling using ondol[J].Korean Journal of Air-Conditioning and Refrigeration Engineering,2000,12(2):200-208.
- [2] 唐凯,周翔,张恩泽,等.辐射吊顶+置换通风系统冬季室内环境舒适性试验研究[J].流体机械,2011,39(6):54-58.
- [3] 隋学敏,刘佳露,黄李雪子,等.地源热泵—辐射供冷/暖复合系统研究现状与展望[J].制冷与空调,2019,33(2):193-202.
- [4] 黄立志,李念平,何颖东,等.不同辐射供冷方式下室内热舒适和能耗模拟分析[J].建筑科学,2017,33(8):90-96.
- [5] Shin M S,Rhee K N,Sang Park H,et al.Enhancement of cooling capacity through open-type installation of cooling radiant ceiling panel systems[J].Building and Environment,2019(148):417-432.
- [6] Ning Baisong,Chen Youming,Liu Hui,et al.Cooling capacity improvement for a radiant ceiling panel with uniform surface temperature distribution[J].Building and Environment,2016(102):64-72.
- [7] Okamoto S,Kitora H,Yamaguchi H,et al.A simplified calculation method for estimating heat flux from ceiling radiant panels[J].Energy and Buildings,2010(42):29-33.
- [8] 唐凯,张旭,刘畅,等.辐射吊顶供冷除湿特性研究与实测分析[J].流体机械,2011,39(6):59-63.
- [9] 冉广鹏,傅允准.转轮除湿新风与毛细管辐射供冷联合运行试验研究[J].流体机械,2018,46(5):78-82.
- [10] 刘前龙,傅允准.毛细管辐射加独立新风系统供冷性能实验研究[J].实验技术与管理,2015,32(7):58-62.
- [11] 毛磊,李维,罗汉,等.顶棚辐射供冷与新风联合系统的辐射顶棚热特性研究[J].低温与超导,2015,43(2),79-83.
- [12] 郎卫国.独立新风+吊顶冷辐射空调与变风量空调系统应用比较[J].发电与空调,2016,37(3):92-94.
- [13] 史德福,金梧凤,陈华.一种新型毛细管冷吊顶辐射板性能研究[J].建筑科学,2012,28(10):55-58.
- [14] 李旺,戴石良,王汉青,等.基于CFD模拟的厨房简易顶板辐射空调模型的研究[J].流体机械,2019,47(4):76-82.
- [15] 康智强,彭馨莹,程小聪,等.国内复合辐射供冷空调系统研究现状[J].流体机械,2017,45(10):68-71.
- [16] 史德福,陈华,金梧凤,等.辐射顶板供冷性能测试方法和计算方法[J].建筑热能通风空调,2012,8(4):7-9.
- [17] Jeong J,Mumma S A.Practically cooling capacity estimation for a suspended mental ceiling radiant cooling panel[J].Building and Environment,2007(9):3176-3185.
- [18] ASHRAE.ASHRAE Hand book-HVAC System and equipment[M].Atlanta:American Society of Heating,Refrigerating and Air-Conditioning Engineers Inc,2008.