复合式露点间接及板管式间接蒸发冷却器的试验研究Experimental Study on Combined Dew Point Indirect And Plate-tube Type Indirect Evaporative Cooler
张鸿;黄翔;杨立然;褚俊杰;贺红霞;
ZHANG Hong;HUANG Xiang;YANG Li-ran;CHU Jun-jie;HE Hong-xia;Xi'an Polytechnic University;
摘要(Abstract):
在一定的二/一次风量比、水气比情况下,对复合式露点间接蒸发冷却器及板管式间接蒸发冷却器的湿球效率、降温幅度、间歇性喷水时间、耗水量等性能参数进行试验分析,并对这2种冷却器的性能特点及适用性进行对比分析。当风量接近2 000 m3/h时,板管式间接蒸发冷却器流道较宽,使用灵活,适用性较强;而复合式露点间接蒸发冷却器降温效果、湿球效率、产冷量更大,但其相应的耗水量也更大。
Experimental analysis was carried out on the performance parameters such as the wet bulb efficiency,range of cooling,intermittent water spray time and water consumption of the combined dew point indirect evaporative cooler and plate-tube indirect evaporative cooler at a certain secondary/primary air volume ratio and water-air ratio.The performance characteristics and applicability of the two coolers were compared and analyzed. When the air flows of the two coolers are close to 2000 m3/h时,板管式间接蒸发冷却器流道较宽,使用灵活,适用性较强;而复合式露点间接蒸发冷却器降温效果、湿球效率、产冷量更大,但其相应的耗水量也更大。
Experimental analysis was carried out on the performance parameters such as the wet bulb efficiency,range of cooling,intermittent water spray time and water consumption of the combined dew point indirect evaporative cooler and plate-tube indirect evaporative cooler at a certain secondary/primary air volume ratio and water-air ratio.The performance characteristics and applicability of the two coolers were compared and analyzed. When the air flows of the two coolers are close to 2000 m3/h,the plate-tube indirect evaporative cooler has a wide flow passage,flexible use and strong applicability,whereas the combined dew point indirect evaporative cooler has the advantages of greater cooling effect,wet bulb efficiency and cooling capacity,but its corresponding water consumption is also greater.
关键词(KeyWords):
复合式露点;性能参数;板管式间接;蒸发冷却
combined dew point;performance parameters;plate-tube indirect;evaporative cooling
基金项目(Foundation): 国家自然科学基金项目(51676145);; “十三五”国家重点研发计划项目(2016YFC0700404)
作者(Authors):
张鸿;黄翔;杨立然;褚俊杰;贺红霞;
ZHANG Hong;HUANG Xiang;YANG Li-ran;CHU Jun-jie;HE Hong-xia;Xi'an Polytechnic University;
参考文献(References):
- [1]麦索特森科V.用于露点蒸发冷却器的方法和板设备:中国,01819555.5[P].2001.9.27.
- [2]Ala Hasan.Indirect evaporative cooling of air to a sub-wet bulb temperature[J].Applied Thermal Engineering,2010(30):2460-2468.
- [3]刘佳莉,黄翔,孙哲,等.新型复合式露点间接蒸发冷却空调机组的试验研究[J].流体机械,2014,42(5):61-66.
- [4]黄翔,刘鸣,于向阳.我国新疆地区蒸发冷却技术应用现状分析[J].制冷与空调,2001(6):33-38.
- [5]黄翔,韩正林,宋姣姣,等.蒸发冷却通风空调技术在国内外数据中心的应用[J].制冷技术,2015(2):47-53.
- [6]黄翔.国内外蒸发冷却空调技术研究进展(2)[J].暖通空调,2007,37(3):32-37.
- [7]宋姣姣.交叉式露点间接蒸发冷却空调机组在通信机房/基站中的应用研究[D].西安:西安工程大学,2015.
- [8]董晓杰.蒸发冷却空调机组耗水量的计算与测试研究[D].西安:西安工程大学,2016.
- [9]夏青,黄翔,殷清海.对淋水密度及相关术语的探讨[J].洁净与空调技术,2013(1):50-52.
- [10]郭赟.干空气能间接蒸发冷水系统与传统制冷空调的技术经济对比[J].中文科技期刊数据库工程技术:全文版,2016(12):275-276.