基于温度互相关原理的制冷剂系统流量现场非侵入式检测研究
Field non-invasive detection of refrigerant system flow based on the principle of temperature cross-correlation

方元,樊海彬,周钦,马翼,刘剑,张小松
Fang Yuan,Fan Haibin,Zhou Qin,Ma Yi,Liu Jian,Zhang Xiaosong

摘要(Abstract):

针对目前暖通空调行业内现场制冷剂流量检测在非侵入性与便捷性等方面存在的问题,基于随机过程互相关理论提出了一套新型非侵入式现场检测系统。研究以温度数据为采集对象,通过测量获取2组互相关的温度信号,进行降噪、互相关计算处理后,可计算确定机组的制冷剂体积流量;再根据温度补偿修正方法,结合压损计算确定制冷剂状态点,可进一步计算实际系统运行的质量流量。通过理论构建与试验验证相结合的方式,对该现场检测系统的可行性与测量效果进行了研究,以一台变频户式空气源热泵(冷热水)机组为被测对象,设计了现场检测试验系统。试验结果表明,对于本试验待测热泵机组,在不同制热工况下其制冷剂流量实测精度基本保持在10%以内,满足实际现场检测的需求。本研究可实现对现场在用机组的非侵入式检测,并且检测系统安装便捷、操作简单,可为暖通空调领域在用机组的性能检测提供参考。
Aiming at the shortcomings of current industry practices in field refrigerant flow detection regarding non-invasiveness and portability,this paper proposes a novel non-invasive field detection system based on the cross-correlation theory of stochastic process.The study focuses on temperature data acquisition, obtaining two sets of mutually correlated temperature signals through measurement.After undergoing noise reduction and cross-correlation calculations,the refrigerant volume flow rate of the chiller can be determined. Subsequently,by applying temperature compensation correction methods and integrating pressure loss calculations to determine the refrigerant's state point,the actual mass flow rate during system operation can be further calculated. By combining theoretical construction with experimental verification,the feasibility and measurement effect of the on-site detection system were studied, and an on-site detection experimental system was designed for a variable frequency air source heat pump(for both heating and cooling water).The experimental results indicate that, for the heat pump unit to be tested in this experiment,the actual measurement accuracy of the refrigerant flow under different heating conditions can generally be maintained within 10%, meeting the needs of actual on-site detection.This study enables non-invasive testing of on-site operating units,and the testing system is easy to install and operate,providing a reference for convenient-invasive performance testing of operating units in the HVAC field.

关键词(KeyWords): 现场检测;互相关原理;非侵入;制冷剂流量
field test;cross-correlation principle;non-invasive;refrigerant flow rate

Abstract:

Keywords:

基金项目(Foundation): 国家自然科学基金项目(52506006);; 江苏省基础研究计划项目(BK20230846)

作者(Author): 方元,樊海彬,周钦,马翼,刘剑,张小松
Fang Yuan,Fan Haibin,Zhou Qin,Ma Yi,Liu Jian,Zhang Xiaosong