以广州新白云机场主航站楼分层空调系统为研究对象,利用CFD对其部分区域进行数值模拟,分析得到空调区温度为25~26℃之间,整个大厅垂直区域温差最大值为9.5℃。大厅大部分区域风速都在0.2~0.4m/s之间,基本满足室内风速设计要求。整个大厅温度分层明显,不辜负分层空调系统可以节能的初衷。
Simulate the stratified air conditioning system of Guangzhou Baiyun airport's main terminal by CFD.The temperature of air-conditioned area are 25~26℃,and the temperature difference is 9.5℃ in vertical region.The speeds of the most of the lobby are 0.2~0.4m/s,which meet the design requirements on the whole.The temperature stratification is significant throughout the hall,to the stratified air conditioning system can be energy-saving in mind.