CO_2热泵热水器多毛细管组合节流特性的研究Study on Throttling Characteristic of Multiple Capillary Combination Used in CO_2 Heat Pump Water Heater
崔海亭,刘东岳,赵华丽,张振国
CUI Hai-ting,LIU Dong-yue,ZHAO Hua-li,ZHANG Zhen-guo
摘要(Abstract):
基于CO_2作制冷剂应用于热泵系统的优良特性,搭建空气源热泵热水系统试验台,进行了单根毛细管、双毛细管、3根毛细管并联组合分别作为节流元件的对比试验,结果表明采用3根毛细管并联组合节流时具有全天候平均COP最高,并得出各温度阶段适用毛细管组合规律,为提高CO_2热泵热水器制热能效提出理论依据。
Based on the excellent properties of carbon dioxide as refrigerant,experimental setup of air-source heat pump hot water system is designed. Experiments are conducted to compare the efficiency of the single,double and three capillary parallel combination respectively. The results show that the three-parallel one has the highest average COP value at the whole day. At the same time,the law of capillary opening and closing at different range of temperature was put forward. This paper lays a theoretical foundation for improving the heat efficiency of heat pump water heaters based on carbon dioxide.
关键词(KeyWords):
CO2;热泵热水器;组合毛细管;COP
carbon dioxide;heat pump water heater;combined capillary tube;COP
基金项目(Foundation): 河北省石家庄市科学技术研究与发展计划项目(161080101A)
作者(Author):
崔海亭,刘东岳,赵华丽,张振国
CUI Hai-ting,LIU Dong-yue,ZHAO Hua-li,ZHANG Zhen-guo
参考文献(References):
- [1]杨礼桢,岑敏婷,王劲柏.热泵热水器变工况下毛细管节流特性探讨[J].流体机械,2011,39(6):74-79.
- [2]王栋,李蒙,戚利利,等.二氧化碳制冷系统毛细管的设计及实验研究[J].化工学报,2011(10):2753-2758.
- [3]熊涛.二氧化碳热泵双毛细管组合节流特性及系统热力性能研究[D].昆明:昆明理工大学,2014.
- [4]张春路,丁国良.毛细管两级串联节流特性[J].上海交通大学学报,2001(8):1178-1181.
- [5]张春路,丁国良,李灏.绝热毛细管性能模拟的平均参数模型[J].上海交通大学学报,1999(8):20-24.
- [6]马娟丽,刘昌海,周骞.膨胀阀开度对跨临界CO2制冷系统损失影响的实验研究[J].西安交通大学学报,2014,48(3):12-16.
- [7]龚毅,梁志礼,侯峰,等.CO2跨临界循环水源热泵系统的试验研究[J].郑州轻工业学院学报(自然科学版),2011,26(4):41-44.
- [8]王晶,赵远扬,李连生.跨临界CO2制冷系统中绝热毛细管性能模拟研究[J].西安交通大学报,2011,45(11):16-21.
- [9]梁志礼,龚毅,任延武,等.跨临界CO2制冷系统性能的实验研究[J].建筑科学,2010,26(10):202-204.
- [10]陈江平,刘军朴,金纪峰.跨临界CO2节流短管流量特性实验研究[J].上海交通大学学报,2005(8):1214-1217.
- [11]王哲,龚毅,吴学红,等.跨临界CO2双节流阀热泵系统的实验研究[J].制冷学报,2012,33(6):57-62.
- [12]Bin Hu,Yaoyu Li,Feng Cao.Extremum seeking control of COP optimization for air-source transcritical CO2heat pump water heater system[J].Applied Energy,2015,147:361-37.
- [13]Neeraj Agrawal,Souvik Bhattacharyya.Parametric study of a capillary tube-suction line heat exchanger in a transcritical CO2heat pump cycle[J].Energy Conversion and Management,2008,48:2979-2985
- [14]孙涛,郭宪民,杨明.毛细管长度对热泵热水器系统动态性能的影响[J].流体机械,2009,37(8):58-62.
- [15]邵双全,石文星,李先庭.空调系统制冷剂充灌量与毛细管长度的优化匹配研究[J].流体机械,2002,30(2):45-48.
- [16]朱兴旺,时阳.毛细管长度对制冷系统性能影响的探讨[J].轻工机械,2002(3):61-63.
- [17]赵宗彬,朱斌祥,李金荣,等.空气源热泵干燥技术的研究现状与发展展望[J].流体机械,2015,43(6):76-81.
- [18]金光,王正文,吴晅,等.混合式土壤源热泵系统的研究现状及展望[J].流体机械,2016,44(2):82-88.
- [19]杨敏官,绍腾,高波,等.熔盐泵分流式空间导叶内部流动及其非定常特性[J].排灌机械工程学报,2015,33(4):306-310.
- [20]Jing Wang,Feng Cao,Zhizhong Wang.Numerical simulation of coiled adiabatic capillary tubes in CO2transcritical systems with separated flow model including metastable flow[J].International Journal of Refrigeration,2012,35:2188-2198.