蒸发冷却与半导体制冷相结合分体式蒸发空调器的试验研究Experimental Study on Split Evaporative Air Conditioner of Evaporative Cooling and Semiconductor Refrigeration
孙哲,黄翔,刘佳莉
SUN Zhe,HUANG Xiang,LIU Jia-li
摘要(Abstract):
设计制作了蒸发冷却与半导体制冷相结合分体式蒸发空调器的试验样机,在标准的空调焓差检测实验台上,模拟室内外侧空气温湿度,在室外侧干球温度34℃,湿球温度18~23℃之间的工况下,对该分体式蒸发空调器的冷水的温度、流量,冷风的温湿度进行了试验。结果表明,该分体式蒸发空调器在室外工况湿球温度20℃以下不开启半导体制冷装置即可满足需要;配合4组半导体制冷装置即可满足室外工况湿球温度23℃时需要,同时也保证了半导体制冷装置较高的能效比;得出了该分体式蒸发空调器的最佳气水比为2,亚湿球效率为110%。进而为分体式蒸发空调器的优化设计与产品开发奠定基础。
Experimental prototype of split evaporative air conditioner of evaporative cooling and semiconductor refrigeration is developed.Simulating the outdoor and indoor air,it is under operating conditions that the outdoor dry-bulb temperature is 34℃,wet-bulb temperature is between 18℃ and 23℃.The water temperature and flow,air temperature and humidity of split air conditioning is tested.The results shows that it doesn't need semiconductor refrigeration device under the wet-bulb temperature of 20℃ in outdoor conditions.To tie four groups semiconductor refrigeration device,it can meet the temperature of water which system needed under wet-bulb temperature of 23℃ in outdoor conditions.Also it guarantees a higher EER of semiconductor refrigeration device.It obtains the best air-water ratio is about 2 and sub-wet bulb efficiency is about 110%.And thus lay the foundation for the optimization of design and product development for the split air-conditioning.
关键词(KeyWords):
蒸发冷却;半导体制冷;分体式蒸发空调器;试验研究;亚湿球效率;气水比
evaporative cooling;semiconductor refrigeration;evaporative air conditioner;experimental study;sub-wet bulb efficiency;air-water ratio
基金项目(Foundation): 西部地区利用干空气可再生能源的节能低碳型蒸发冷却空调开发与应用(2011KTCQ01-10);; 陕西省科技统筹创新工程计划项目(2012—2015)
作者(Author):
孙哲,黄翔,刘佳莉
SUN Zhe,HUANG Xiang,LIU Jia-li
参考文献(References):
- [1]黄翔.蒸发冷却空调理论与应用[M].北京:中国建筑工业出版社,2010.
- [2]黄翔,孙铁柱,汪超.蒸发冷却空调技术的诠释(1)[J].制冷与空调,2012,12(2):1-6.
- [3]王恒月.制冷能效比更高的空调器[J].暖通空调资讯,2011,(10):94-95.
- [4]孙哲,黄翔,汪超,等.蒸发冷却与半导体制冷相结合的空调系统初探[J].化工学报,2012,(S2):156-160.
- [5]孙哲,黄翔,范坤,等.与蒸发冷却相结合的半导体制冷装置性能分析[J].西安工程大学学报,2013,27(1):88-92.
- [6]魏小兵,江楠,曾纪成.新型纵向流油冷却器传热性能及压降的试验研究[J].压力容器,2012,29(6):9-13.
- [7]黄翔,白延斌,郝航.蒸发冷却冷水机组出水温度探讨[J].流体机械,2012,40(9):83-86.
- [8]宣永梅,黄翔,康宁.采用蒸发冷却的辐射供冷空调系统室内热环境模拟验证[J].流体机械,2012,40(10):80-83,57.
- [9]白延斌,黄翔,孙铁柱,等.气水比对蒸发冷却高温冷水机组出水温度的影响[J].流体机械,2011,39(10):83-86.