喷雾冷却塔气水比和截面风速对冷却效率的影响
Influence of the Air/Water Ratio and the Cross-section Velocity on Cooling Efficiency in Spraying Cooling Tower

路建岭,赵惠忠,邹志军,黄晨
LU Jian-ling,ZHAO Hui-zhong,ZOU Zhi-jun,HUANG Chen (University of Shanghai for Science and Technology

摘要(Abstract):

根据雾化冷却原理,建立了80 t/h试验用逆流式无填料喷雾冷却塔,并通过4个工况的试验分析了气水比和截面风速对喷雾冷却塔冷却效率的影响,试验结果表明:冷却效率随气水比、截面风速的增加而增大,当截面风速从1.93m/s增加到3.21m/s时,气水比从1.04增加到1.31,冷却效率随之从39.0%增加到54.5%;当气水比在1.16~1.20之间保持不变或变化较小时,可以通过增大塔内截面风速来提高冷却塔的冷却效率。
According to the principle of atomization cooling,a 80t/h experimental counter-flow no-padding spraying cooling tower was established.And through four experimental conditions the influence of the air/water ratio and the cross-section velocity on cooling efficiency in spraying cooling tower was analyzed.The results showed: the cooling efficiency would increase when the air/water ratio and the cross-section velocity increased,for example when the cross-section velocity changed from 1.93m/s to 3.21m/s,meanwhile the air/water ratio changed from 1.04 to 1.31,and the cooling efficiency would change from 39.0% to 54.5% consequently;if the air/water ratio remained unchanged or had a smaller change from 1.16 to 1.20,the cooling efficiency of the cooling tower could be improved by the way of increasing the cross-section velocity.

关键词(KeyWords): 喷雾冷却塔;二次雾化装置;气水比;截面风速;冷却效率
spraying cooling tower;secondary-atomization device;air/water ratio;cross-section velocity;cooling efficiency

Abstract:

Keywords:

基金项目(Foundation): 上海市研究生创新基金项目(JWCXSL0802);; 上海市教委重点学科建设项目(J50502);; 国家自然科学基金(50478113);; 国家科技支撑计划(2006BAJ02A05)

作者(Author): 路建岭,赵惠忠,邹志军,黄晨
LU Jian-ling,ZHAO Hui-zhong,ZOU Zhi-jun,HUANG Chen (University of Shanghai for Science and Technology

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享