北京地区空气源热泵供暖系统的应用研究Study on the Application of Air Source Heat Pump Heating System in Beijing Area
胡文举,张帅,李德英,张啊文
HU Wen-ju,ZHANG Shuai,LI De-ying,ZHANG A-wen
摘要(Abstract):
针对北京地区空气源热泵散热器供暖系统进行了实测研究,对系统运行期间的各房间空气温度、机组供回水温度及散热器表面温度、系统供热量、耗电量进行了实测。测试结果表明,该系统能够满足室内热舒适性的要求,室内温度维持在15℃以上,且温度分布均匀;供热系统性能稳定,供热量和制热性能系数COP都能保持在稳定状态,测试期内供热系统的COP约为2.8。
Based on the experimental study of air source heat pump system in Beijing area,the air temperature,the temperature of the supply water and return water and the radiator surface temperature,heating capacity of the system and power consumption were measured.The test results show,the system can satisfy the indoor thermal comfort,indoor temperature is maintained at 15℃,and the temperature distribution is uniform;the heating system performance stability,heat capacity and COP can be maintained in a stable state,COP of the heating system test period is about 2.8.
关键词(KeyWords):
空气源热泵;供暖;舒适性;COP
air-source heat pump;heating;riding comfort;COP
基金项目(Foundation): 国家自然科学基金项目(51508016);; 研究生培养—产学研联合培养研究生基地(市级)(2015年)资助项目(31062015001)
作者(Author):
胡文举,张帅,李德英,张啊文
HU Wen-ju,ZHANG Shuai,LI De-ying,ZHANG A-wen
参考文献(References):
- [1]宋为民,董重成,李庆娜.散热器采暖低温运行的研究[J].中国建筑金属结构,2010(5):36-39.
- [2]Ala Hasan,Jarek Kurnitski,Kai Jokiranta.A combined low temperature water heating system consisting of radiators and floor heating[J].Energy and Buildings,2009,41(5):170-179.
- [3]李庆娜.散热器采暖系统低温运行应用研究[D].哈尔滨:哈尔滨工业大学,2009.
- [4]张又升,赵敬德,王金龙.空气源热泵室外换热器翅片管的融霜过程分析[J].流体机械,2016,44(6):66-71.
- [5]王子介.辐射采暖住宅建筑能耗与室内作用温度[J].南京师范大学学报:工程技术版,2002,2(2):78-83.
- [6]许可,王树刚,蒋爽,等.空气源热泵用于低温热水地板辐射供暖系统的模拟研究[J].制冷技术,2014(1):12-17.
- [7]黄宝玉,李家坤.空气源热泵在供热水系统中的应用[J].长江工程职业技术学院学报,2009,26(3):50-51.
- [8]李雄志,王汉青,张杰,等.长沙地区空气源热泵地板采暖系统实测分析[J].制冷与空调,2007,7(6):71-75.
- [9]史丽娜,刘学来,李永安,等.电驱动和燃气驱动空气源热泵运行设备的分析[J].流体机械,2016,44(8):78-82.
- [10]周斌,谭洪卫,王亮,等.上海地区空气源热泵散热器供暖系统应用研究[J].暖通空调,2013,43(9):83-86
- [11]于涛,乔春珍,赵玉清,等.空气源热泵+散热器低温采暖在北京农村地区应用的综合性分析[J].节能,2014(12):51-53,54.
- [12]Air-conditioning,Heating and Refrigeration Institute.ANSI/AHRIStandard551/591-2011(SI),Performance rating of water-chilling and heat pump water-heating packages using the vapor compression cycle[S].USA:Arlington,2011.