流体机械

2017, v.45;No.542(08) 64-67

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Past Issue) | 高级检索(Advanced Search)

组合式空调机组不同断面风速均匀度对供冷/热量的影响
Influence of Different Section Wind Speed Uniformity on Cooling/Heat of Combined Air-conditioning Unit

谢鸿玺;谢宝刚;谢添玺;包继虎;彭飞;
XIE Hong-xi;XIE Bao-gang;XIE Tian-xi;BAO Ji-hu;PENG Fei;Hefei General Machinery Research Institute;Tianjin University;

摘要(Abstract):

对空调系统中调节空气状态的关键设备──组合式空调机组进行试验研究,相同工况、相同风量的机组处理空气能力随着断面风速均匀度不同而变化。试验发现,在额定风量分别为5000,10000,20000 m3/h的机组的供冷量、供热量随着断面风速均匀度从75%到98%变化时,机组的供冷量分别增加2.214,5.347,9.858 k W,供热量分别增加3.137,8.18,12.603 k W,即随着额定风量的增大,断面风速均匀度对机组的供冷量、供热量影响增大,当断面均匀度达到90%时,影响增幅变缓。
The experimental study on the key equipment which adjust the air state in the air conditioning system—the Combined Air-conditioning Unit, the same conditions, the same amount of air handling capacity of the unit with the section wind speed uniformity varies. The test found that the rated air volume of 5000,10000,20000 m3/h unit cooling capacity, heat supply with the section wind speed uniformity from 75% to 98% change, the unit cooling capacity Respectively, increased 2.214, 5.347, 9.858 k W, heat supply increased 3.137, 8.18, 12.603 k W, both with the increase of rated air flow, wind speed uniformity of the unit on the cooling capacity, heat supply increased, when the sectional uniformity reaches 90%, the increase of the influence becomes slow.

关键词(KeyWords): 组合式空调机组;断面风速均匀度;供冷量;供热量
combined air-conditioning unit;section wind speed uniformity;cooling capacity;heat supply

Abstract:

Keywords:

基金项目(Foundation):

作者(Authors): 谢鸿玺;谢宝刚;谢添玺;包继虎;彭飞;
XIE Hong-xi;XIE Bao-gang;XIE Tian-xi;BAO Ji-hu;PENG Fei;Hefei General Machinery Research Institute;Tianjin University;