数据中心机房空调系统设计及气流优化分析
Air Conditioning System Design and Air Distribution Optimization for the Date Centre Room

陈修敏,张九根
CHEN Xiu-min,ZHANG Jiu-gen

摘要(Abstract):

以江苏省某数据中心机房为研究对象,简要介绍了该中心机房空调系统空调方式、气流组织、新风系统、消防排烟系统、高密度制冷方案的的设计。通过CFD软件模拟分析数据中心主机房的气流组织情况,针对主机房出现的局部热点、气流组织不畅等问题,提出气流优化方案,模拟仿真结果验证了气流组织优化设计的有效性。
Taking a data center room of jiangsu as the study object,describes the design of air conditioning mode,air distribution,outdoor air system,smoke control and extraction system,refrigeration scheme of the air conditioning system briefly. Then uses CFD software to simulate and analyze the air distribution situation of the data center main room. Aiming at problems of local hot spots,poor air distribution in the room,puts forward the airflow optimization scheme,and the simulative result shows that the air distribution optimization design is effective.

关键词(KeyWords): 数据中心机房;空调系统;CFD;气流优化
data center room;air conditioning system;CFD;airflow optimization