数据中心机房空调系统设计及气流优化分析Air Conditioning System Design and Air Distribution Optimization for the Date Centre Room
陈修敏,张九根
CHEN Xiu-min,ZHANG Jiu-gen
摘要(Abstract):
以江苏省某数据中心机房为研究对象,简要介绍了该中心机房空调系统空调方式、气流组织、新风系统、消防排烟系统、高密度制冷方案的的设计。通过CFD软件模拟分析数据中心主机房的气流组织情况,针对主机房出现的局部热点、气流组织不畅等问题,提出气流优化方案,模拟仿真结果验证了气流组织优化设计的有效性。
Taking a data center room of jiangsu as the study object,describes the design of air conditioning mode,air distribution,outdoor air system,smoke control and extraction system,refrigeration scheme of the air conditioning system briefly. Then uses CFD software to simulate and analyze the air distribution situation of the data center main room. Aiming at problems of local hot spots,poor air distribution in the room,puts forward the airflow optimization scheme,and the simulative result shows that the air distribution optimization design is effective.
关键词(KeyWords):
数据中心机房;空调系统;CFD;气流优化
data center room;air conditioning system;CFD;airflow optimization
基金项目(Foundation):
作者(Author):
陈修敏,张九根
CHEN Xiu-min,ZHANG Jiu-gen
参考文献(References):
- [1]孙研.通信机房节能综合解决方案[J].电信工程技术与标准化,2006,(6):26-29.
- [2]刘成,陈乐天,王颖.通信机房空调气流组织合理化研究[J].建筑热能通风空调,2010,10(29):80-84.
- [3]李红霞.通信机房空调节能气流优化措施[J].邮电设计技术,2011,9(3)6-8.
- [4]孙云雷,王丽慧.地铁活塞风与空调送风耦合的温度场的试验研究[J].流体机械,2012,40(11):61-65.
- [5]黄艳山,邓伟雄,廖坚卫.广州白云机场主航站楼空调气流组织模拟研究[J].流体机械,2011,39(11):81-83.
- [6]齐洪洋,高磊,张莹莹,等.管壳式换热器强化传热技术概述[J].压力容器,2012,29(7):77-82.
- [7]GB50174-2008电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
- [8]吴灵敏.IDC机房空调设计浅析[J].空调设计,2008,(12):55-58.
- [9]查贵庭,张勇,李新权.冷池技术让数据中心更环保[J].中国教育网络,2012,(10):57-58.
- [10]赖世能,侯福平,宗凌.IDC机房上下送风方式空调系统分析比较[J].电信技术,2005,(11):33-35.
- [11]ASHRAE.Datacom equipment power trends and applications[EB/OL].[2014-02-08].Http://tc99.ashraecs.org.