采用微通道蒸发器的分离式热管空调传热性能的试验研究Experimental Investigation on the Heat Transfer performance of the Separate Type Heat Pipe Air Conditioning with a Microchannel Evaporator
胡张保,张志伟,李改莲,邵双全,胡手槟
HU Zhang-bao,ZHANG Zhi-wei,LI Gai-lian,SHAO Shuang-quan,HU Shou-bin
摘要(Abstract):
设计了一套采用微通道换热器作为蒸发器的分离式热管空调,并试验研究了充液率、室内外温差和风机风量等因素对其传热性能的影响。试验结果表明:充液率过大过小均会影响系统的传热性能,其最佳充液率为120%左右;室内外温差越大分离式热管空调传热效果越好,空调传热量在室内外温差为20℃时比室内外温差为8℃时增加了228%;当风机风量低于2000m3/h时,传热量和EER随着风量的增加而增大,当风机风量超过2000m3/h时,增加风量对传热量的影响减小,而EER开始呈现下降趋势。
A separate type heat pipe air conditioning unit with a microchannel evaporator was designed,and a few factors which would affect the heat transfer performance of the separate type heat pipe air conditioning such as filling rate,temperature difference between the indoor air and the outdoor and air volume were experimentally studied. The results showed that heat transfer performance of the system was affected by filling rate,and the optimal filling rate was about120%. The larger the temperature difference between the indoor air and the outdoor was,the better the heat transfer effect was,and the heat-transfer content would increase 228% when the temperature difference between the indoor air and the outdoor changed from 8℃ to 20℃. The heattransfer content and EER increased with the increase of the air volume,and the influence of increasing air volume on the heattransfer content decreased slowly when the air volume over 2000m3/ h,and EER began to decrease.
关键词(KeyWords):
分离式热管;微通道换热器;充液率;风量
separate type heat pipe;microchannel heat exchanger;filling rate;air volume
基金项目(Foundation): 国家科技支撑计划课题(2012BAA13B03);; 佛山市院市合作项目(2013HK100462);; 郑州轻工业学院大学生创新试验项目(2015122)
作者(Author):
胡张保,张志伟,李改莲,邵双全,胡手槟
HU Zhang-bao,ZHANG Zhi-wei,LI Gai-lian,SHAO Shuang-quan,HU Shou-bin
参考文献(References):
- [1]蒋青泉.通信网络能耗分析与节能技术应用[J].中南大学学报(自然科学版),2009,(2):464-470.
- [2]Yau Y H.The use o f a double heat pipe heat exchanger system for r educing energy consumption of treating ventilation air in an operating theatre-a full year energy consumption model simulation[J].Energy and Buildings,2008,40(5):917-925
- [3]Zheng Y,Li Z,Liu X,et al.,Retrofit of Air-Conditioning System in Data Center Using Separate Heat Pipe System,in Proceedings of the 8th International Symposium on Heating,Ventilation and Air Conditioning,A.Li,Y.Zhu,and Y.Li,Editors.2014,Springer Berlin Heidelberg.p.685-694.
- [4]Kuang YW,Wang W,Zhuan R,et al.Simulation of Boiling Flow in Evaporator of Separate Type Heat Pipe with Low Heat Flux[J].Annals of Nuclear Energy,2015,75:158-167.
- [5]薛志虎,曲伟.脉动热管稳态运行的理论模型研究[J].流体机械,2013,41(4):70-74.
- [6]史维秀,潘利生.脉动热管理论及技术进展[J].流体机械,2013,41(7):72-77.
- [7]韩同行,左超平,秦加明,等.蒸汽发生器传热管流弹失稳计算[J].压力容器,2014,31(11):39-44.
- [8]Tang Z,Liu A,Jiang Z.Two Phase Flow and Heat Transfer Characteristics of a Separate-Type Heat Pipe[J].Heat and Mass Transfer,2011,47(7):841-846.
- [9]陈岚,苏俊林,伍贻文.分离式热管充液率实验研究[J].上海理工大学学报,2003,25(3):285-288.
- [10]郝莹,臧润清,金育义.以R600a为工质的分离式热管的实验研究[J].低温与超导,2009,37(12):37-41.
- [11]王爱辉,罗高乔,汪韩送.重力式热管空调机组运行特性试验研究[J].制冷技术,2013,33(2):14-16.
- [12]赵展,金苏敏.基于管排组合的分离式热管换热器的数值模拟[J].流体机械,2011,39(7):83-86+67.
- [13]金鑫,瞿晓华,祁照岗,等.分离式热管型机房空调性能实验研究[J].暖通空调,2011,41(9):133-136.
- [14]Choi J,Jeon J,Kim Y.Cooling performance of a hybrid refrigeration system designed for telecommunication equipment rooms[J].Applied Thermal Engineering,2006,27(11):2026-2032.
- [15]Lee S,Kang H,Kim Y.Performance optimization of a hybrid cooler combining vapor compression and natural circulation cycles[J].International Journal of Refrigeration,2008,32(5):800-808.
- [16]Manimaran R,Palaniradja K,Alagumurthi N,et al.Experimental comparative study of heat pipe performance using Cu O and Ti O2nanofluids[J].Int.J.Energy Res.,2014,38(5):573-580.
- [17]Rahmat M,Hubert P.Two-Phase Simulations of Micro Heat Pipes[J].Computers&Fluids,2010,39(3):451-460.
- [18]张剑飞,秦妍,孔祥国.扁管和百叶窗式微通道换热器空气侧阻力的实验研究[J].制冷学报,2014,35(1):88-91.
- [19]金育义,臧润请,顾永明.分离式热管在不同高度差下传热性能的实验研究[J].应用能源技术,2009(04):45-47+51.
- [20]GB/T 7725-2004房间空气调节器[S].
- [21]庄俊,张红.热管技术及其工程应用[M].北京:化学工业出版社,2000.
- [22]GB50174-2008.电子信息系统机房设计规范[S].北京:中国计划出版社,2008.