流体机械

2010, v.38;No.460(10) 53-57

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

变频滚动转子压缩制冷系统‘0’过热度性能影响试验研究
Experimental Study on the Effect of '0' Superheat on the Inverter Rotary Compressor Refrigerant System Performance

韩磊,陶乐仁,黄礼号,杨志强,张淑红
HAN Lei,TAO Le-ran,Huang Li-hao,YANG Zhi-qiang,ZHANG Shu-hong(University of Shanghai for Science and Technology

摘要(Abstract):

将膨胀阀开度连续变化使蒸发器出口由大过热度到一定量的回液这一过程分为四种情形,通过试验了解系统及压缩机在各状态下的性能。结果表明:压缩机在30Hz到80Hz各频率下,过热度从10~70℃降到蒸发器出口大量回液,系统性能系数均在‘0’过热有最高点。相对于过热度2~70℃制冷量Q0增大4%~12%,COP提高6%~13%,在‘0’过热后回液量进一步加大系统性能降低,但在‘0’过热点附近蒸发器出口存在明显震荡。
Liquid-Refrigerant return is divided into four case by amount of liquid Refrigerant from evaperator.Experiments are carried out to investigate the effect of different superheat and liquid refrigerant floodback degree on the performance of inverter unit and rotary compressor.When compressor vary from 30hz to 80 hz,the results indicated that system perfomence coefficient reach the highest points at '0'superheat point.Cooling capacity increased by 4%~12% compred with 2~70℃ superheat degree cases,while COP icreased by 6%~13%.Performance characteristics decreased with the amount of Liquid-Refrigerant return,leading to periodic oscillation of the refrigeration cycle.

关键词(KeyWords): ‘0’过热度;滚动转子压缩机;回气带液;变频制冷系统
'0'superheat;rotary compressor;liquid refrigerant floodback;inverter refrigeration system

Abstract:

Keywords:

基金项目(Foundation): 国家高技术研究发展计划资助项目(863计划)(No.2008AA05Z204)

作者(Author): 韩磊,陶乐仁,黄礼号,杨志强,张淑红
HAN Lei,TAO Le-ran,Huang Li-hao,YANG Zhi-qiang,ZHANG Shu-hong(University of Shanghai for Science and Technology