R32热泵示范系统运行性能的试验研究Experimental Research on Operation Performance of R32 Heat Pump Demonstration System
贾磊;陈松;黄磊;何亚峰;吴俊峰;潘祖栋;
Jia Lei;Chen Song;Huang Lei;He Yafeng;Wang Rujin;Pan Zudong;State Key Laboratory of Compressor Technology,Anhui Province Key Laboratory of Compressor Technoloty,Hefei General Machinery Research Institute Co.,Ltd.;Zhejiang Dun An Artificial Environment Group Co.,Ltd.;Hefei General Environment Control Technology Co.,Ltd.;
摘要(Abstract):
针对某医院示范改造项目应用R32空气源热泵系统的供暖运行性能开展试验研究,分析示范建筑的环境温度及室内温度变化情况,计算R32热泵系统的总制热量、总能耗和供暖季综合性能系数,并研究系统在低环境温度下的运行情况。结果表明,R32空气源热泵的供暖效果良好,整个供暖季的系统综合性能系数为2.91,室内平均温度达17.8℃,在环境温度为-12.5℃左右时,R32空气源热泵系统的供水温度约为41℃,平均系统能效为2.2。
Experimental research was conducted for a demonstrative reconstruction project of a hospital-the operating performance of R32 air-source heat pump application. The environmental temperature and indoor temperature change of the demonstration building were analyzed,the total heating capacity,total energy consumption and the heating season comprehensive performance coefficient of the R32 air-source heat pump system were calculated,and operation performance of the system under low environmental temperature was studied. The results show that the R32 air-source heat pump had better heating effect. The comprehensive performance coefficient of the system in the whole heating season was 2.91,the average indoor temperature reached17.8 ℃,and when the ambient temperature was -12.5 ℃,the water supply temperature of the heat pump system was about 41 ℃and the average energy efficiency of the system was 2.2.
关键词(KeyWords):
R32;空气源热泵;运行性能;系统能效
R32;air-source heat pump;operation performance;system energy efficiency
基金项目(Foundation): 国家重点研发计划资助项目(2016YFF0201504)
作者(Authors):
贾磊;陈松;黄磊;何亚峰;吴俊峰;潘祖栋;
Jia Lei;Chen Song;Huang Lei;He Yafeng;Wang Rujin;Pan Zudong;State Key Laboratory of Compressor Technology,Anhui Province Key Laboratory of Compressor Technoloty,Hefei General Machinery Research Institute Co.,Ltd.;Zhejiang Dun An Artificial Environment Group Co.,Ltd.;Hefei General Environment Control Technology Co.,Ltd.;
参考文献(References):
- [1]张新玉,郭宪民,张森林.R32中间补气压缩空气源热泵系统的试验研究[J].流体机械,2015,43(5):61-64.
- [2]潘李奎,肖芳斌,尹茜,等. R32喷气增焓空气源热泵的试验研究[J].制冷与空调,2017,17(5):86-91.
- [3]汪涛,王芳,陈红群,等. R32用于喷气增焓热泵热水器中可行性研究[J].建筑节能,2017,45(1):139-144.
- [4]康伟,韩欣欣,徐洪波,等.轨道交通车辆低环境温度空气源热泵用制冷剂的性能比较[J].制冷与空调,2017,17(12):42-46.
- [5]史敏,贾磊,钟瑜,等.R32用于单元式空调机的性能实验研究[J].制冷与空调,2011,11(2):78-80.
- [6]罗宝军,刘琦.基于准等温压缩的空气源热泵理论分析[J].工程热物理学报,2018,39(2):237-241.
- [7]孔祥强,乔尚游,李俊枭.不同工质的热泵热水器热力学性能分析[J].制冷,2017,36(1):77-82.
- [8]孔维利,屠冰,李旻阳.R32空气源热泵机组性能试验研究[J].制冷与空调,2013,13(1):48-51.
- [9]孟照峰,王芳,李堂,等.冬季工况下R32热泵性能的试验研究[J].流体机械,2015,43(2):66-69.
- [10]王路路,张华,邱金友.R1234ze(E)与R32混合工质在热泵系统中替代R410A的实验研究[J].制冷学报,2017,38(3):30-35.
- [11]薛杰,郭宪民,薛利平.带闪发器中间补气的R32空气源热泵系统性能实验研究[J].低温与超导,2017,46(4):88-91.
- 贾磊
- 陈松
- 黄磊
- 何亚峰
- 吴俊峰
- 潘祖栋
Jia Lei- Chen Song
- Huang Lei
- He Yafeng
- Wang Rujin
- Pan Zudong
- State Key Laboratory of Compressor Technology
- Anhui Province Key Laboratory of Compressor Technoloty
- Hefei General Machinery Research Institute Co.
- Ltd.
- Zhejiang Dun An Artificial Environment Group Co.
- Ltd.
- Hefei General Environment Control Technology Co.
- Ltd.
- 贾磊
- 陈松
- 黄磊
- 何亚峰
- 吴俊峰
- 潘祖栋
Jia Lei- Chen Song
- Huang Lei
- He Yafeng
- Wang Rujin
- Pan Zudong
- State Key Laboratory of Compressor Technology
- Anhui Province Key Laboratory of Compressor Technoloty
- Hefei General Machinery Research Institute Co.
- Ltd.
- Zhejiang Dun An Artificial Environment Group Co.
- Ltd.
- Hefei General Environment Control Technology Co.
- Ltd.